These requirements should not be mixed. A CPU with a newer suffix may share the same SR60 designation but still require different firmware, engineering software or validation work. For a production line with a narrow shutdown window, the correct spare is usually the unit that restores operation with the fewest uncontrolled changes.
What the Siemens 6ES7288-1SR60-0AA0 Provides
According to the official Siemens technical data, its core specifications include:
|
Product description |
SIMATIC S7-200 SMART CPU |
|
Onboard digital inputs |
36 × 24 VDC |
|
Onboard digital outputs |
24 × relay, up to 2 A |
|
Power supply |
85–264 VAC, 47–63 Hz |
|
Program memory |
30 KB |
|
Data memory |
20 KB |
|
Typical bit-operation time |
150 ns per instruction |
|
Typical word-operation time |
1.2 µs per instruction |
|
Typical floating-point time |
3.6 µs per instruction |
|
Maximum power loss |
25 W |
|
Dimensions |
175 × 100 × 81 mm |
|
Operating temperature |
0–55°C, horizontal installation |
|
Programming software |
STEP 7 Micro/WIN SMART |
|
Protection rating |
IP20 |
The CPU is a standard controller, not a fail-safe PLC. Emergency stops, guard switches and other safety functions therefore require an appropriately designed and validated safety circuit.
Where the 6ES7288 Series Fits on the Factory Floor
Motion-heavy applications need another decision. If the machine includes registration control, electronic gearing or high-frequency PTO commands, an ST-series transistor-output CPU may be more appropriate than the SR relay version. Siemens’ newer S7-200 SMART V3.0 platform adds expanded memory and PLCopen-oriented motion capabilities, but V3.0 hardware cannot simply be treated as a drop-in firmware upgrade for every older CPU.
Recommended Siemens 6ES7288 Modules and CPU Options
The correct bill of materials depends on signal count, output technology and installed firmware. The following Siemens automation parts cover several common retrofit configurations:
Brand and product description
Order number
Practical use
Siemens SIMATIC S7-200 SMART CPU SR60 AC/DC/Relay
6ES7288-1SR60-0AA0
Like-for-like maintenance of an established SR60 installation; 36 DI and 24 relay outputs
Siemens SIMATIC S7-200 SMART CPU SR60 V3.0 AC/DC/Relay
6ES7288-1SR60-0AA2
Newer SR60 projects requiring expanded memory; migration and software compatibility must be checked
Siemens SIMATIC S7-200 SMART SM DR32 Digital I/O Module
6ES7288-2DR32-0AA0
Adds 16 × 24 VDC inputs and 16 × 2 A relay outputs
Siemens SIMATIC S7-200 SMART SM DT32 Transistor Digital I/O Module
6ES7288-2DT32-0AA0
Adds 16 digital inputs and 16 sourcing transistor outputs rated at 0.75 A
Siemens SIMATIC S7-200 SMART SM DT32 Transistor Digital I/O Module
6ES7288-3AM06-0AA0
Four analog inputs and two analog outputs for pressure, flow, level and speed-reference signals
Siemens SIMATIC S7-200 SMART SM AI08 Analog Input Module
6ES7288-3AE08-0AA0
Eight analog inputs supporting common voltage and 0/4–20 mA instrumentation
Do not select a module from channel count alone. Check the CPU’s expansion-bus power budget, module sequence, panel width, field supply, load grouping, isolation requirements and ambient-temperature derating.
What Engineering and Procurement Should Confirm Before Ordering